Product Description; General Information About The Ev3 Drive; Drive Highlights; Models - Emerson EV3150B Application Manuallines

Ev3 inverter drive for zpv* & ypv* variable speed compressors
Table of Contents

Advertisement

2

Product description

2.1

General information about the EV3 drive

The EV3 inverter drive has been developed specifically for Copeland scroll compressor models
ZPV066/096 and YPV066/096. These are variable speed compressors with permanent magnet
synchronous motors. The drive will power the compressor, control the compressor running speed,
provide compressor and drive protection and communicate with the master controller. The drive has
integrated fans for cooling and is typically installed in a system near the compressor.
2.2

Drive highlights

The EV3 drive at a glance:
▪ Control of Copeland variable speed ZPV*/YPV* compressors in commercial environments
▪ Predefined selection for compressor
▪ Active envelope protection
▪ Special envelope related overload protection
▪ Compressor crankcase heater functionality
▪ Operation ambient temperatures -25 to 60 °C
▪ Controllable via RS485 and Modbus
▪ Automatic baud rate detection (19.200 bps)
▪ Designed and qualified based on EN 60335-1 for the European market
▪ UL 60730-1 approval for the North American market
▪ Safety Input to wire a high-pressure limiter
▪ Discharge line temperature sensor input (DLT)
▪ Integrated passive power factor correction
▪ Integrated EMI filter
▪ Inrush-current limitation
▪ Rated currents @ 50 °C
▪ Enclosure with integrated heatsink and fan for cooling
▪ Speed-Drop Protection mode for increased system stability
2.3

Models

Power supply
Drive model
50/60 Hz
EV3150B
3~ 380 to 460 VAC
EV3185B
3~ 380 to 460 VAC
Table 3: Voltage, current and power range
NOTE: The power range in Table 3 is to be considered as an indication depending on the
system design and compressor motor. The rated voltage to run ZPV*/YPV* compressors in
the full dedicated envelope and to pass EN 60335-2-34 tests is 400 VAC for three-phase drives.
2.4

Advanced technical information

Storage temperature
Max. operating temperature
Max. full performance operating temperature
Humidity
Altitude
Pollution degree
Drive enclosure protection
DC choke protection
Communication
Sensor input
Safety torque off input
Max. efficiency
Max. power factor
Table 4: Advanced technical information
4
®
RTU
Max. input
Max. output
current @ 50 °C
current @ 50 °C
27 A
27 A
38 A
38 A
-40 to +85 °C
-25 to +65 °C
-20 to +50 °C
0 to 95 % rH non-condensing
Max. 2000 m above sea level
2
IP20
IP00
RS485 Modbus (RTU)
Baud rate 19.200 bps
Slave ID: 45
Discharge line temperature
DLT / NTC 10 kΩ
Designed to connect a safety high-pressure limiter
~98 %
~0.94 w/ integrated PPFC
Max. input
power @ 380 V
15 kW
18.5 kW