Analog input 3
8
Default function
Type of input
Mode controlled by...
Operating in Voltage mode (default)
Voltage range
Absolute maximum voltage range
Operating in thermistor input mode
Supported thermistor types
Trip threshold resistance
Reset resistance
Short-circuit detection resistance
9
Analog output 1
10
Analog output 2
Terminal 9 default function
Terminal 10 default function
Type of output
Voltage range
Maximum output current
Protection
11
0V common
Function
21
0V common
Function
+24 V User output (selectable)
22
Terminal 22 default function
Programmability
Nominal output current
Maximum output current
Protection
23
0V common
Function
E300 Design Guide
Issue Number: 1
Electrical
Getting
User Menu A Commissioning
installation
started
Motor thermistor input
Bipolar single-ended analog voltage, or thermistor input
Parameter F52
± 10 V ± 2 %
± 36 V relative to 0 V
Din 4408, KTY 84, PT100, PT 1000, PT 2000
User defined in parameter F60
User defined in parameter F61
50 Ω ± 40 %
SPEED / FREQUENCY output signal
Motor torque producing current
Bipolar single-ended analog voltage output
±10 V ± 5 %
± 20 mA
20 mA max. Short circuit protection
Common connection control terminals 1 to 11
Common connection control terminals 21 to 31
+24 V User output
Can be switched Off (0) or On (1) to act as a fourth digital output (positive logic only)
by setting the source F29 and source invert F32
100 mA combined with DIO3
100 mA
200 mA total (including all Digital I/O)
Current limit and trip
Common connection control terminals 21 to 31
Advanced
Diagnostics Optimization CT MODBUS RTU Technical Data
Parameters
71