Installing The Gsd; Setting The Address - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

4.6.2.3

Installing the GSD

Procedure
To install the GSD of the inverter in the engineering system of the controller, proceed as follows:
1. Save the GSD on your PC via one of the following methods.
– From the Internet:
– From your inverter:
2. Unzip the GSD file on your computer.
3. Import the GSD in the engineering system of the controller.
You have now installed the GSD file in the engineering system of the controller.
4.6.2.4

Setting the address

Valid addresses: 1 ... 125
Procedure
Proceed as follows to set the PROFIBUS address:
1. Set the address using one of the subsequently listed options:
– Via the address switch
– On an operator panel via p0918
– With STARTER or Startdrive
2. Switch off the inverter supply voltage.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
Insert a memory card into the inverter and then set p0804 = 12.
The inverter writes the GSD as zipped file (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
Overview of the interfaces (Page 91)
After you have changed the address in STARTER, select the button "RAM to ROM"
.
4.6 Connecting the inverter to the fieldbus
You have the following options for setting the PROFI‐
BUS address:
● Using the address switch on the Control Unit:
The address switch has priority over the other
settings.
● With the parameter p0918 (factory setting:
p0918 = 126):
It is only possible to change p0918 if an invalid
address is set in the address switch.
● With STARTER or Startdrive:
Setting is only possible if an invalid address is set
in the address switch.
Installing
127

Advertisement

Table of Contents
loading