L7: Torque Limit - YASKAWA U1000 iQpump MATRIX Drive User Manual

Low harmonic regenerative pump controller
Hide thumbs Also See for U1000 iQpump MATRIX Drive:
Table of Contents

Advertisement

u

L7: Torque Limit

No.
(Addr.
Name
Hex)
L7-01
(04A7) Forward Torque Limit
L7-02
(04A8) Reverse Torque Limit
L7-03
Forward Regenerative
(04A9)
Torque Limit
L7-04
Reverse Regenerative
(04AA)
Torque Limit
L7-06
Torque Limit Integral
(04AC)
Time Constant
Torque Limit Control
L7-07
Method Selection during
(04C9)
Accel/Decel
L7-16
Torque Limit Process at
(0444D)
Start
u
L8: Drive Protection
No.
(Addr.
Name
Hex)
L8-02
(04AE) Overheat Alarm Level
L8-03
Overheat Pre-Alarm
(04AF)
Operation Selection
L8-07
Output Phase Loss
(04B3)
Protection Selection
L8-09
Output Ground Fault
(04B5)
Detection Selection
L8-10
Heatsink Cooling Fan
(04B6)
Operation Selection
L8-11
Heatsink Cooling Fan
(04B7)
Off Delay Time
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
LCD Display
OLV
OLV
OLV
OLV
Torq Limit Fwd
Sets the torque limit value as a percentage of the motor rated
torque. Four individual quadrants can be set.
Torq Limit Rev
Torq Lmt Fwd Rgn
Torq Lmt Rev Rgn
OLV
OLV
OLV
OLV
Trq Lim I Time
Sets the integral time constant for the torque limit.
OLV
OLV
OLV
OLV
0: Proportional control (changes to integral control at constant
Trq Lim d AccDec
speed). Use this setting when acceleration to the desired speed
P-ctrl @ Acc/Dec
should take precedence over the torque limit.
I-ctrl @ Acc/Dec
1: Integral control. Set L7-07 to 1 if the torque limit should take
precedence.
TLim DlyTime Sel
OLV
OLV
OLV
OLV
0: Disabled
0: Disabled
1: Enabled
1: Enabled
LCD Display
An overheat alarm occurs when heatsink temperature exceeds the
L8-02 level.
OH Pre-Alarm Lvl
OH Pre-Alarm Sel
0: Ramp to stop. A fault is triggered.
0: Ramp to Stop
1: Coast to stop. A fault is triggered.
1: Coast to Stop
2: Fast Stop. Decelerate to stop using the deceleration time in
2: Fast-Stop
C1-09. A fault is triggered.
3: Alarm Only
3: Continue operation. An alarm is triggered.
4: Run@L8-19 Rate
4: Continue operation at reduced speed as set in L8-19.
0: Disabled
1: Enabled (triggered by a single phase loss)
Outp Ph Loss Det
2: Enabled (triggered when two phases are lost)
0: Disabled
Note:
1: 1PH Loss Det
2: 2/3PH Loss Det
Grnd Flt Det Sel
0: Disabled
0: Disabled
1: Enabled
1: Enabled
0: Run with timer (Fan operates only during run and for L8-11
seconds after stop.)
1: Run always (Cooling fan operates whenever the drive is
Fan On/Off Sel
powered up.)
0: Dur Run (OffDly)
1: Always On
Note:
Sets a delay time to shut off the cooling fan after the Run
Fan Delay Time
command is removed when L8-10 = 0.
Description
Output Torque
Positive Torque
L7-01
L7-04
Regeneration
REV
Regeneration
L7-03
L7-02
Negative Torque
Description
Output phase loss detection can mistakenly be
triggered if the motor rated current is very small
compared to the drive rated output current. Disable
this parameter in such cases.
If a damping resistor overheat (doH) is detected,
the cooling fan will turn on regardless of the setting
value.
B.9 L: Protection Function
Values
Default: 200%
Min.: 0
Max.: 300
Default: 200%
Min.: 0
Max.: 300
Motor
Default: 200%
r/min
Min.: 0
FWD
Max.: 300
Default: 200%
Min.: 0
Max.: 300
Default: 200 ms
Min: 5
Max: 10000
Default: 0
Range: 0, 1
Default: 1
Range: 0, 1
Values
<1>
Default:
Min.: 50 °C
Max.: 150 °C
Default: 3
Range: 0 to 4
Default: 1
Range: 0 to 2
Default: 1
Range: 0, 1
Default: 0
Range: 0, 1
Default: 300 s
Min.: 0
Max.: 300
Page
Page
B
319