H3: Multi-Function Analog Inputs - YASKAWA Z1000 User Manual

Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

B.7 H Parameters: Multi-Function Terminals
H2-oo
Function
Setting
Function 0 to b2 with
inverse output
Note: A prefix of "!" is
100 to
added to represent
1B2
inverse functions on the
LCD keypad display.
Example: "!Zero speed"
u

H3: Multi-Function Analog Inputs

No.
(Addr.
Name
Hex)
H3-01
Terminal A1 Signal
(410)
Level Selection
H3-02
Terminal A1 Function
(434)
Selection
H3-03
Terminal A1 Gain
(411)
Setting
H3-04
Terminal A1 Bias
(412)
Setting
H3-09
Terminal A2 Signal
(417)
Level Selection
H3-10
Terminal A2 Function
(418)
Selection
H3-11
Terminal A2 Gain
(419)
Setting
H3-12
Terminal A2 Bias
(41A)
Setting
H3-13
Analog Input Filter Time
(41B)
Constant
H3-14
Analog Input Terminal
(41C)
Enable Selection
H3-16
Terminal A1 Offset
(2F0)
H3-17
Terminal A2 Offset
(2F1)
308
H2 Multi-Function Digital Output Settings
LCD Display
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
LCD Display
0: 0 to 10 V with zero limit
Term A1 Level
1: 0 to 10 V without zero limit
0: 0-10V,
2: 4-20 mA
(LowLim=0)
3: 0-20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A1.
Term A1 FuncSel
Sets the level of the input value selected in H3-02 when 10 V
is input at terminal A1.
Terminal A1 Gain
Sets the level of the input value selected in H3-02 when 0 V is
input at terminal A1.
Terminal A1 Bias
0: 0 to 10 V with zero limit
Term A2 Level
1: 0 to 10 V without zero limit
0: 0-10V,
2: 4 to 20 mA
(LowLim=0)
3: 0 to 20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A2.
Term A2 FuncSel
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Terminal A2 Bias
Sets a primary delay filter time constant for terminals A1 and
A1/A2 Filter T
A2. Used for noise filtering.
Determines which analog input terminals will be enabled when
A1/A2 Sel
a digital input programmed for "Analog input enable"
1: A1 Available
(H1-oo = C) is activated.
2: A2 Available
1: Terminal A1 only
3: A1/A2 Available
2: Terminal A2 only
3: Terminals A1 and A2
Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0
Term A1 Offset
Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0
Term A2 Offset
Description
Description
Use jumper switch S1 to set input terminal A1
for current or voltage.
Use jumper switch S1 to set input terminal A2
for current or voltage input signal.
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Page
Values
Page
Default: 0
176
Range: 0 to 3
Default: 0
177
Range: 0 to 26
Default: 100.0%
Min.: -999.9
137
Max.: 999.9
Default: 0.0%
Min.: -999.9
137
Max.: 999.9
Default: 2
177
Range: 0 to 3
Default: 0
177
Range: 0 to 26
Default: 100.0%
Min.: -999.9
137
Max.: 999.9
Default: 0.0%
Min.: -999.9
137
Max.: 999.9
Default: 0.03 s
Min.: 0.00
Max.: 2.00
Default: 2
Range: 1 to 3
Min.: -500
Max.: 500
Min.: -500
Max.: 500