H3: Multi-Function Analog Inputs - YASKAWA Z1000 Technical Manual

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

5.8 H: Terminal Functions
Status
Open
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Closed
Drive is outputting frequency.
Setting 39: Watt Hour Pulse Output
Outputs a pulse to indicate the watt hours.
Setting 3D: During Speed Search
The output terminal closes while Speed Search is being performed.
Setting 4C: During Fast Stop
The output terminal closes when a Fast Stop is being executed. .
Setting 4D: oH Pre-Alarm Time Limit
The output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat
alarm has not disappeared after 10 frequency reduction operation cycles.
Setting 60: Internal Cooling Fan Alarm
The output closes when the drive internal cooling fan has failed.
Setting 100 to 160: Functions 0 to 60 with Inverse Output
These settings have the same function as settings 0 to 60, but with inverse output. Set as 1oo, where the "1" indicates inverse
output and the last two digits specify the setting number of the function.
Examples:
• Set 108 for inverse output of "8: During Baseblock 1 (N.O.)".
• Set 14D for inverse output of "4D: oH Pre-Alarm Time Limit".
u

H3: Multi-Function Analog Inputs

The drive is equipped with multi-function analog input terminals: A1 and A2.
Settings on page 163
for a listing of the functions that can be set to these terminals.
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1. Set jumper S1 on the terminal board accordingly for voltage input or current
input.
No.
H3-01
Setting 0: 0 to 10 V with Zero Limit
The input level is 0 to 10 Vdc with zero limit. The minimum input level is limited to 0%, so that a negative input signal due
to gain and bias settings will be read as 0%.
160
OFF
ON
run command
baseblock
OFF
command
output
frequency
OFF
ON
during run
OFF
during frequency
output
Figure 5.33 During Frequency Output Time Chart
Name
Terminal A1 Signal Level Selection
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Description
ON
ON
Refer to Multi-Function Analog Input Terminal
Setting Range
0 to 3
Default
0