Commissioning
5.5
5.6
5-8
48XX/49XXSHB0399

Changing the internal control structure

The internal control structure is adapted to the control task (e. g. speed control,
torque control, angle control, ¡) via code C005 (see chapter 7.9). The controller
must however be inhibited first.
Stop!
It is possible that the terminal assignments change when the internal control
structure is changed.

Changing the terminal assignment

Note!
A function, which is already assigned to an input, can only be assigned to another
terminal if the input used before is assigned with a new function.
If you reassign an input, the function assigned before will be overwritten.
Freely assignable digital inputs
Except for the functions "Enable JOG setpoints", "Enable additional acceleration
and deceleration times", "Enable fix setpoints" and "Select parameter set", each
function can only be assigned to one input.
It is possible to determine a priority for each input:
The function can either be switched via a terminal, or depending on the selected
operating mode.
Changing the assignment
1. Select the input to be assigned under C112.
2. Select the function for the input under C113.
3. Determine the polarity under C114 (HIGH-active or LOW-active).
4. Determine the priority under C115.
Repeat steps 1. to 4. to assign all inputs.
5 freely assignable inputs are available at the terminals.