Operating Modes - Lenze 4800 Manual

Dc speed controller
Table of Contents

Advertisement

Show/Hide Bookmarks
Configuration
7.8.5
Code
Code
Name
Name
C001¤ Operating
mode
7-116
48XX/49XXSHB0399

Operating modes

The controller can be adapted to your application in different ways:
Terminals:
The terminals are to control the controller.
Operating unit:
There are five keys and the plain text display on the operating
unit for parameter setting and control of the controller.
LECOM1:
LECOM1 is a protocol for control and parameter setting of the
unit via a PC or other hosts. The signals are processed to the
interface standards RS232C and RS485. The controller can be
connected to a superimposed system via X6.
LECOM2:
For very difficult requirements, the controller can be parameter-
set and operated with LECOM2 via fieldbus connection
modules for standard bus systems (InterBus-S, PROFIBUS
etc.).
Possible settings
Lenze Selection
0
Control
-0-
Terminals Keypad
-1-
Keypad
-2-
Terminals LECOM1
-3-
LECOM1
-4-
Terminals LECOM2 (*)
-5-
LECOM2 (*) LECOM2 (*)
-6-
LECOM2 (*) Keypad
-7-
LECOM2 (*) LECOM1
Note!
With control via keypad, LECOM1 and LECOM2, the terminal functions controller
enable (X1/28), quick stop (X1/21 and X1/22) and the additional setpoint (X1/6)
remain the same in the configurations C005 = -1X-, -4X-, -5X-.
Parameter setting
Keypad
LECOM1
Info
With C001 =
-2-, -3-, -4-, -5-, -7-, TRIP must be reset
(C043) via the interface or the terminal.
With LECOM2, TRIP reset is also possible
via the control word of the process data
channel.
(*) Fieldbus