Lenze 4800 Manual page 250

Dc speed controller
Table of Contents

Advertisement

Show/Hide Bookmarks
Display
OUE
Mains overvoltage
P03
Following error
P13
Angle overflow
PER
Program interference
PR
Parameter reset
PR1 ... PR4 Parameter set error
Sd1
Tacho fault
Sd2
Resolver fault
Sd3
Encoder fault at Dig_In 1 Incremental encoder or digital frequency cable
Sd4
Encoder fault at Dig_In 2 Incremental encoder or digital frequency cable
Sd5
Master current
interrupted
SP
Wrong signal source
polarity
–15V supply interfered
U15
Troubleshooting and fault elimination
Cause
Mains voltage > 460V or 550V (500V variant) Reduce mains voltage with a preconnected
Angle difference between set and actual
position is larger than the following error limit
set under C255
Drive cannot follow the digital frequency (I
limit)
Angle controller limit reached
Drive cannot follow the digital frequency (I
limit)
A fault in the program sequence was detected Send controller with data (on diskette) to
After switching on, a change in the software
version has been detected.
Automatic loading of factory setting.
Fault when reading a parameter set
CAUTION:
The factory setting is loaded automatically
Short circuit or interruption of tacho cable
Resolver cable interrupted
interrupted at X5
Input X5 PIN 8 not assigned
interrupted at X9
Input X9 PIN 8 not assigned
Interruption of the master current selection,
I
< 2mA
master
with master current selection 4...20mA, C034
= -1-
Tacho, resolver or fieldbus connection are
interchanged
Overload / short-circuit terminal 20
–15 V supply defective
Remedy
transformer or
use a controller with a higher mains
connection voltage.
Extend following limit with C255
Switch-off monitoring if required (C119/C120)
Enable drive (Ctrl. enable)
Check drive dimensioning
max
Enable drive
Check drive dimensioning
max
Lenze
Set the required parameters and save settings
under C003.
Set the required parameters and save settings
under C003.
Check tacho cables for short-circuit or
interruption and remove fault
Check resolver cable for open circuit
Check resolver
Acknowledge fault by mains switching
Check cable for open circuit
Assign input X5 PIN 8 with encoder potential
or switch off monitoring (C119 / C120)
Assign input X9 PIN 8 with encoder potential
or switch off monitoring (C119 / C120)
Remove interruption of the set-value cable or
select master selection 0...20 mA under C034
= -0-
Change tacho, resolver or fieldbus connection
Check load at terminal 20
Return controller