Example
The analog inputs terminal 8 and terminal 6 are to be connected (division) via the
arithmetic block 2 and then be assigned to the code C046 "main set-value".
Procedure
( Select C145 = -4-, terminal 8
( Assign C146 = -14-, arithmetic block 2 input 1
( Select C145 = -3-, terminal 6
( Assign C146 = -15-, arithmetic block 2 input 2
( Select C145 = -10-, arithmetic block 2
( Assign C146 = -1-, main set-value (C046)
( C191 = -4-, division: select input 1 / input 2 (C338 / C339).
3. Functions
For all arithmetic blocks the following functions can be preselected (example for
arithmetic block 2):
with C191 = -0-, output
with C191 = -1-, output
with C191 = -2-, output
with C191 = -3-, output
with C191 = -4-, output
with C191 = -5-, output
Arithmetic block 1 (fixed)
Code
Code
Name
Name
C190*¤ Arithmetic
block 1
100%
50%
100%
1%
200%
Possible settings
Lenze Selection
1
-0-
Output = C046
-1-
Output = C046 + C049
-2-
Output = C046 - C049
Output = C046 ¼ C049
-3-
-4-
Output = C046 / |C049|
-5-
Output = C046 / (100% - C049)
= C338 (C339 not processed)
= C338 + C339
= 50% + 50%
= C338 - C339
= 100% - 50%
= C338
C339
:
= 100%
100%
:
= C338 / |C339|
= 100% / 100%
= C338 / (100% - C339)
= 100% / (100% - 50%)
Info
Configuration
48XX/49XXSHB0399
7-71