Commissioning
Freely assignable analog monitor outputs
Via the monitor outputs X4/62, X4/63 und X8, internal signals can be output as
voltage signals, current signals or frequency signals (See chapter 4.3.4.1).
With C108 and C109 (C109 is not effective for the digital frequency output), the
outputs can be adapted, for instance, to a measuring unit or a slave drive.
Changing the assignment
1. Select the output to be assigned under C110.
2. Select the function for the output under C111.
3. Set the offset under C109 (not for the digital frequency output).
4. Determine the gain under C108.
Repeat steps 1. to 4. until all outputs are assigned.
Special feature of the freely assignable digital frequency output
With the selection of a configuration under C005, the output X8 already has a basic
assignment. The assignment can only be changed afterwards.
If the digital frequency output X8 is assigned to another signal than indicated in the
basic assignment of the configuration (C005),then the output frequency can only
be adapted via code C108.
With signal sources with a reference value of 100% (see C111, except: DF and
resolver inputs) a signal of 100% at the output X8 with a gain factor of
C108 = 1.00 corresponds to a frequency of 250 kHz.
5-10
48XX/49XXSHB0399