7.4.4

Standstill excitation (field heating)

Purpose
With this function, a reduced field current can be set as field heating to avoid
condensation in the event of motor standstill.
FIG 7-21
Code
Code
Name
Name
C316* Reduced
field current
C317* Time delay
for the
reduced
field current
C318* Activate
field current
reduction
Standstill excitation
Possible settings
Lenze Selection
20 % 0 % I
{1 % I
Frated
Frated
60 s
0.0 s
{0.1 s}
10 s
{1 s}
100 s
{10 s}
0
-0-
Field current reduction function is switched off
-1-
Field current reduction function is switched on
Info
}
100 % I
Reference: I
Frated
With selection 0%, the ignition pulses of
the field controller are inhibited.
10 s
Time which is required to activate the
reduced field current after inhibiting the
100 s
controller.
3600 s
Configuration
4900Str048
(C083)
Frated
48XX/49XXSHB0399
7-61