Components Of The Ce-Typical Drive System; Measures Required - Lenze 4800 Manual

Dc speed controller
Table of Contents

Advertisement

Show/Hide Bookmarks
Installation
4.4.2
System component
Controller
RFI filter
Mains choke
Armature and field cable
Control cables
Encoder cable for digital frequency
Encoder cable for resolver
Motor
Accessories
4.4.3
4-30
48XX/49XXSHB0399

Components of the CE-typical drive system

Specification
4800/4900 DC controllers
For data and filters see chapter 13.4
For assignment and technical data see chapter 13.2
Unscreened power cable
Rated max. length: 50m
Screened signal cable type LIYCY
Lenze system cable or screened signal cable, twisted in pairs, tin plated E-CU braid
with 75% optical overlay
Lenze system cable type EWLR or screened signal cable, twisted in pairs, tin plated
E-CU braid with 75% optical overlay
Separately excited DC motor
Lenze series MGFQ, MGFR or similar
InterBus module 2110IB
Profibus module 2130IB
Controller, RFI filter and mains choke are mounted on the same assembly board
inside a standard control cabinet.

Measures required

Control cabinet assembly board
( For HF grounding, only use mounting plates with an excellent conductive
surface (e.g. zinc-coated surface).
( If you use mounting plates with badly conductive surfaces (e.g. painted,
anodized, yellow passivated):
- Remove the paint or coating from the contact surface of the mains filters,
controllers, and screen connections, to provide a large and conductive
connection.
( When using several mounting plates, connect them with a surface as large
as possible (e.g. using copper bands).
( Connect the controller, RFI filter and mains choke to the grounded
mounting plate with a surface as large as possible.
Power connection
( Avoid unnecessarily long cables
( Ensure the separation of motor cable and signal or mains cable.
( Ensure separation of unscreened and screened cables (distance > filter
length)
( Ensure a distance as short as possible between the conductors
(single-cores)
( Both ends of unused cores should be connected to ground/PE.