Lenze 4800 Manual page 159

Dc speed controller
Table of Contents

Advertisement

Show/Hide Bookmarks
Configuration
4900Str054
FIG 7-27
General signal structure of the process controller
Process controller inputs
1. Analog inputs
With the function "freely assignable analog inputs" (C145...C147) the process
controller inputs "set", "act." and "evaluation" can be assigned to other signal
sources (see table C145).
The inputs "set" and "evaluation" have their own codes (C330 and C331) and can
be parmaterised via keypad or interface. The setting via these codes is however
only possible if these no signal inputs are assigned to these codes.
The inputs "set" and "act." represent the set-value and the actual value of the PID
controller.They are adjustable up to á100%.
With the input "evaluation", the controller output can be weakened or inverted.
Values up to á100% are adjustable. With the evaluation 100%, all process
controller influence is effective.
The inputs "set" and "evaluation" are connected to their own ramp function
generator before being processed any further. Acceleration and deceleration times
can be set separately (C332 to C335).
7-68
48XX/49XXSHB0399