Signal flow
³
Function
ˆ n
n
act
x
Threshold adjustable under C017 from -5000rpm...+ 5000rpm.
Hysteresis fixed 25rpm, default setting: C017 = -3000rpm
l
Purpose
For monitoring the act. speed with torque control C005 = -40-...-43-
l
Output level = LOW
4900SStr118
n-controller output = M
max
Window fixed 99.9% from n-controller output.
Hysteresis fixed 1.9%. The signal is equivalent to I
l
Purpose
4900SStr119
Monitoring of the speed control circuit for limitation (control error)
l
Output level = HIGH
RFG
= RFG
Inp
outp
Window adjustable under C241 from 0...100%
Hysteresis fixed 1% of n
max ,
l
Purpose
Signal for detection of acceleration processes in the set-value channel
l
4900SStr120
Output level = HIGH
n
= 0
act
Threshold adjustable under C019 from 0...5000rpm.
Hysteresis fixed 25rpm, default setting: C019 = 50rpm
l
Purpose
Signal for reliable mains switch-off, standstill detection
l
4900SStr127
Output level = LOW
n
= n
act
set
Window adjustable under C240 from 0...100%.
Hysteresis fixed 25rpm, default setting: C240 = 1%
l
Purpose
Signal for detection of control deviation in the speed control circuit
4900SStr121
l
Output level = HIGH
4900SStr122
Ün
Ü ˜ n
act
x
Threshold adjustable from 100 to + 5000rpm under C242.
Hysteresis fixed 2% of n
max
Default setting: C242 = 1000rpm
l
Purpose
Monitoring of the actual speed for overspeed
4900SStr123
l
Output level = HIGH
ÜC046Ü or ÜC049Ü ˜ n
x
Threshold adjustable from 0 to 100% under C243
Hysteresis fixed, default setting: C243 = 1%
l
Purpose
Starting protection at digital frequency coupling and analog correction signal
l
4900SStr124
Output level = HIGH
Configuration
. LED at the operating unit
max
default setting: C241 = 1%