Lenze 4800 Manual page 221

Dc speed controller
Table of Contents

Advertisement

Show/Hide Bookmarks
Configuration
Code
Code
Name
Name
C112*¤ Input selection:
Freely
assignable
digital input
[C113*] Function for
C112
[C114*] Polarity for
C112
[C115*] Priority for C112
C116*¤ Input selection:
Freely
assignable
digital output
7-130
48XX/49XXSHB0399
Possible settings
Lenze
Selection
1
-1-
digital input X2/E1
-2-
digital input X2/E2
...
-5-
digital input X2/E5
-0-
No function
-1-
Enable additional T
-2-
Enable JOG setpoint (X4/E4, E5)
-3-
TRIP reset (X2/E2)
-4-
TRIP set (X2/E1)
-6-
Switch-off additional setpoint (X4/E3)
-7-
Switch-off I-component of the n-controller
-9-
Ramp function generator stop
-10-
Ramp function generator zero
-16
Motor potentiometer deactivated
-17
Motor potentiometer down
-18
Motor potentiometer up
-20
Select parameter set
-21
Load parameter set
-30-
Deactivate process controller
-31-
Switch-off I-component of the process
controller
-32-
Set the process controller to 0
-40-
Enable fixed setpoint
0
-0-
Input HIGH active
-1-
Input LOW active
-0-
Terminal function not active, if terminal
control is switched-off under C001.
(X2/E4, E5)
-1-
Terminal function remains active, if terminal
control is switched-off under C001.
(X2/E1, E2, E3)
1
-1-
FDO 1
-2-
FDO 2
...
-12-
FDO 12
-13-
Relay output X3/K11, X3/K14
Info
The digital inputs E1..E5 are freely
assignable with the functions under C113.
Each function can only be assigned to one
input. Exceptions:
l
C113 = -20- : max. 2 dig. inputs
l
C113 = -1-, -2-, -40-: max. 4 dig.
inputs (binary coded selection of max.
1, 3, 7 or 15 additional T
setpoints).
Assignment of functions:
1.Select input under C112.
2.Assign function under C113.
3.Determine polarity under C114.
4.Determine priority under C115.
times
i
The digital outputs FDO1..FDO12 and the
relay output X3/K11, X3/K14 are freely
assignable with the functions under C117.
Multiple assignment is possible.
The outputs FDO1...FDO5 are assigned to
the terminals X3/A1...X3/A5.
FDO6...FDO12 can only be accessed via
LECOM.
Assignment of functions:
1.Select output under C116.
2.Assign function under C117.
Only for FDO1...FDO5, relay output:
3.Determine polarity under C118.
4.Determine signal delay under C128.
times or
i

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4900

Table of Contents