Configuration
7.1.3.4
7-18
48XX/49XXSHB0399
( V
control
ab
The field weakening operation is derived from the control level of the V
controller. With this control, the maximum motor voltage is limited to static
V
= 1.05 V
(C090). The dynamic response is adjusted via the
Amax
Arated
parameters for the V
controller and the field controller.
ab
Adjustment of the field weakening operation:
1. Enter I
under C231 (10...100% ref. to I
Fmin
2. Selection of 100% n
3. Increase n
under C011 until reaching the required speed.
max
4. Adjustment of the proportional gain of the V
5. Adjustment of the integral action time of the V
8
8
FIG 7-7
Signal-flow chart (section) for the field control circuit with V
Adjustment of speed controller parameters
C070 V
speed controller
pn
Adapt the drive to different inertias under C070:
1. Increase C070 until the drive becomes instable.
2. Reduce C070 by approx 5 % until the drive becomes stable again.
C071 T
speed controller
nn
The integral action time of the speed controller is set to the lower level current
controller. It is not necessary to optimise it for easy speed controls.
Note!
With T
= 9999ms, the speed controller operates as proportional controller. For
nn
operation with higher-level control circuits with integral action component, the
speed controller should be parameterised as P controller.
Frated
at X1/8.
set
ab
).
controller (C233)
controller (C234)
ab
control
ab
down
4900Str034