7.1.5.4
Freely assignable monitor outputs
The controller is equipped with two analog (terminals 62 and 63) and a digital
(digital frequency output X8) monitor outputs to output internal signals as voltage,
current or frequency signals. The positions of switches S1 and S2 required for the
analog outputs, can be obtained from chapter 4.3.4.1.
If you want to assign a new signal to an output, select under C110 which output
is to be changed. Select under C111 the signal to be assigned to this output. Under
C108 and C09 adjust gain and offset (C109 is not valid for the digital frequency
output) to adapt the monitor output, for instance, to a display instrument.
Stop!
With freely assignable signals positive feedbacks may occur, which can lead to
uncontrolled drive acceleration!
Code
Name
C108*
Gain for
C110
C109*
Offset for
C110
C110*¤ Input
selection:
Monitor
output
Possible settings
Lenze Selection
1.00
-10.000 {0.001} + 10.000
0mV
-10000mV
{1mV}
1
-1-
Analog output X4/62 (monitor 1)
-2-
Analog output X4/63 (monitor 2)
-3-
Digital frequency output X8
Configuration
Info
Gain for X4/62, X4/63, X8
+10000mV
Loading of the factory settings does not
overwrite C109.
Offset for X4/62, X4/63.
This code is only effective, if the digital
frequency output is selected under C110.
The monitor outputs are freely assignable
with the signals under C111:
1.Select monitor output under C110.
2.Assign signals under C111.
3.If necessary, adjust under C108 and
C109.
48XX/49XXSHB0399