4Q / 2Q changeover

Purpose
With a change to 2Q, the armature voltage V
1.05 ¼ V
in 4Q operation.The direction of rotation cannot be changed through
rated
the controller (if necessary, consider the change of the direction of rotation through
active loads).
The changeover is carried out through code C180 of the extended code set when
the controller is inhibited.
With the changeover:
( all set-value paths remain the same.
( the current limit C023 is internally set to 0. It is still possible to enter external
values.
( only bridge 1 is active (motor terminal A is positive).
( the deceleration ramp C105 remains effective at QSP. However, no energy
is fed back to the mains, i.e. the motor is coasting to standstill if the
deceleration times are very short.
Stop!
With 48XX controller, the mode 4Q must not be selected. If the controllers
4808...4813 are set to 4Q operation, the fuses may blow.
FIG 7-20
Signal-flow chart (section) for 2Q operation
can be set to 1.15 ¼ V
A
rated
instead of