7.3
Parameter Settings for a Master Station
This chapter describes the parameter settings when a master/local module is used as a master station.
7.3.1
Setting method
1.
Open the "Network Parameter" window from a programming tool.
Project window
2.
Check the checkbox next to "Set the station information in the CC-Link configuration window" at
the top of the window. (for GX Works2 only)
3.
Input settings to the "Network Parameter" window. (
4.
Click the
5.
Write the settings to the CPU module using the programming tool.
[Online]
6.
The settings are reflected by resetting the CPU module or powering off and on the system. When
the reflection is completed, data link is automatically started at master/local modules.
● To change the settings for a master station or a slave station, stop data link at the master station. (
Section 11.4.5)
● When change the settings for a slave station, change the settings for the master station accordingly.
96
[Parameter]
[Network Parameter]
button.
[Write to PLC]
[CC-Link]
Page 97, Section 7.3.2)
Page 320,