Mitsubishi Electric MELSEC-Q Series User Manual page 222

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

(b) Network parameter of a programming tool
• Do not use a programming tool to set network parameters for the modules where settings are configured
using the G(P).RLPASET instructions. Also do not use the G(P).RLPASET instructions to configure
settings for the modules where network parameters have been set using a programming tool. Doing so
causes abnormal end of the instruction and the settings are not reflected.
• When set "Number of Modules" of the network parameter of a programming tool, do not include the
number of modules that are set using the G(P).RLPASET instruction.
(c) Network parameter change during data link
Network parameters cannot be changed during data link. Therefore, stop the data link using Data link stop
(SB0002) and execute the G(P).RLPASET instruction.
(d) Setting of a status input from a data link faulty station
The setting of a status input from a data link faulty station is not allowed. The input from a data link faulty station
is cleared.
(e) Standby master function
The standby master station cannot be connected. To connect the standby master station, configure settings
using a programming tool.
(f) Output when a CPU module is switched from RUN to STOP
The outputs from the remote output (RY) in the master station to a remote station, local station, intelligent
device station, and standby master station are held. (For the master/local module with a serial number (first five
digits) of 09111 or earlier)
220