(b) Slave station setting data
Device
Item
Set the station type, number of occupied stations, and station number as follows:
The default values are "0101
occupied stations: 1, station type: Ver.1-compatible remote I/O station).
(1)
(2)
Setting for 1
(S2) + 0
to 64
to
*1
(S2) + 63
stations
(3)
*1
Configure settings as many number as the one set for the total module connected of the control data.
*2
Select the intelligent device station for a local station or standby master station.
*3
Setting a value outside the setting range results in abnormal end.
Setting data
b15
to
b12 b11
to
b8 b7
to 0140
H
Station number setting
1 to 64 (BIN setting)
Number of occupied stations setting
Number of occupied stations
1
2
3
4
*2*3
Station type setting
Station type
Ver.1-compatible remote I/O station
Ver.1-compatible remote device station
Ver.1-compatible intelligent device station
Ver.2-compatible remote device station (single)
Ver.2-compatible intelligent device station (single)
Ver.2-compatible remote device station (double)
Ver.2-compatible intelligent device station (double)
Ver.2-compatible remote device station (quadruple)
Ver.2-compatible intelligent device station (quadruple)
Ver.2-compatible remote device station (octuple)
Ver.2-compatible intelligent device station (octuple)
CHAPTER 9 DEDICATED INSTRUCTIONS
to
b0
Station number
Number of occupied stations
Station type
" (station number: 1 to 64, number of
H
Setting
1
H
2
H
3
H
4
H
Setting
C
Setting
Set by
range
1 to 40
H
1 to 4
H
User
0
H
1
H
2
H
5
H
6
H
0 to F
H
8
H
9
H
B
H
H
E
H
F
H
9