Mitsubishi Electric MELSEC-Q Series User Manual page 256

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3.
Set the switch on the CPU module in the master station to RUN to execute the program.
Executing the program turns on Initial data processing request flag (RX18) of the AJ65VBTCU-68ADVN
and AJ65VBTCU-68DAVN. Then the initial setting is executed.
When the initial setting is completed, the input value of the AJ65VBTCU-68ADVN is converted into a
digital value. CH.1 digital output value is stored into D500, and CH.2 digital output value is stored into
D501.
If an error occurs in the AJ65VBTCU-68ADVN, an error code is stored into D508. After the cause of the
error is removed and X25 is turned on, the error is reset.
4.
Turning on X22 sets the digital value of the AJ65VBTCU-68DAVN.
5.
Turning on X23 outputs the analog value from the AJ65VBTCU-68DAVN.
If an error occurs in the AJ65VBTCU-68DAVN, an error code is stored into D518. After the cause of the
error is removed and X26 is turned on, the error is reset.
254