(6) Link special relays (SBs) and link special registers (SWs) related to the remote
device station initialization procedure registration
(a) Link special relays (SBs)
Link special relays (SBs) related to the remote device station initialization procedure registration are listed
below.
Values in parentheses are buffer memory addresses and bit numbers.
• Remote device station initialization procedure registration instruction (SB000D) (5E0
• Execution status of remote device station initialization procedure (SB005E) (5E5
• Completion status of remote device station initialization procedure (SB005F) (5E5
(b) Link special registers (SWs)
Link special registers (SWs) related to the remote device station initialization procedure registration are listed
below.
Values in parentheses are buffer memory addresses.
• Specification of remote device station to be initialized (SW0014 to SW0017) (614
• Remote device station initialization procedure registration instruction result (SW005F) (65F
• Remote device station initialization procedure registration execution individual information (target 1)
(SW0110) (710
information (target 16) (SW011F) (71F
(7) Replacement of a master/local module in failure
When replacing a master/local module in failure with a new master/local module, do not use a module with a
serial number (first five digits) of 08031 or earlier.
If a module with a serial number (first five digits) of 08031 or earlier is used by mistake, and the specification of
remote device station to be initialized is performed, each station operates as listed below.
Master station/remote device
station
Master station
Remote device station
) to Remote device station initialization procedure registration execution individual
H
)
H
The setting of Specification of remote device station to be initialized (SW0014 to SW0017) is
ignored, and the initial process is performed in all the remote device stations set in the network
parameter.
• In a remote device station where a module has been replaced due to failure, the initial process is
completed.
• The initial process may not be completed in a remote device station that is normally operating. If
the initial process is not completed, check Remote device station initialization procedure
registration execution individual information (SW0110 to SW011F).
CHAPTER 8 FUNCTIONS
, b14)
H
, b15)
H
to 617
H
Operation
, b13)
H
)
H
)
H
8
157