8.3

Useful Applications of the Functions

This section describes the useful functions of a master/local module.
8.3.1
Remote device station initialization procedure registration
function
The initial setting of a remote device station, which is performed on a program, can be registered in advance using a
programmable tool and can be saved by turning on the link special relay (SB). A program for the initial setting is not
required.
For example, in an AJ65BT-64AD, settings such as "A/D conversion enable/prohibit specification" and "Averaging
process specification" can be easily configured.
For a setting example using a programming tool, refer to Page 232, Section 10.2.
(1) Number of initial settings registered
(a) Number of remote device stations
The initial settings of up to 16 remote device stations can be registered in one master/local module. Use a
program to register the initial settings of stations after the 17th station.
(b) Number of initial settings registered per remote device station
Up to 16 items of the initial settings can be registered per remote device station. Use a program to register 17
items or more. A programming tool and program cannot be used together for the initial setting in one remote
device station. If they are used together, a remote device station may malfunction.
(2) If the process has stopped
Information about an initial setting in progress is stored in Remote device station initialization procedure
registration execution individual information (SW0110 to SW011F) of a master/local module. If the process has
stopped halfway, information such as the number of the procedure that has stopped and the number of the station
where the procedure has stopped can be checked.
(3) How to configure the initial setting
Configure the setting in "Remote Device Station Initial Setting" of the network parameter in the master station.
Then use Remote device station initialization procedure registration instruction (SB000D) to reflect the initial
setting to the remote device station. (
154
Page 108, Section 7.3.2 (3), Page 232, Section 10.2)