ST:
Constant
(The largest value in the results of 1) to 3) below. When B is 0, the result of 2) is ignored. When C is 0,
the result of 3) is ignored.
1)
800 + (A × 15)
2)
900 + (B × 50)
C  26: 1200 + (C × 100)
3)
C > 26: 3700 + {(C - 26) × 25}
EX:
Constant (only when a master/local module is used in the remote net Ver.2 mode and remote net
additional mode)
50 + total numbers found as listed in the table below
Expanded
Cyclic Setting
Occupied Station 1
Single
Double
70 × number of stations
Quadruple
90 × number of stations
110 × number of
Octuple
stations
RT:
Retry processing time (Only the link scan with a faulty slave station where data link is being performed is
added.)
 + × (number of detected faulty stations -1)
:
Retry processing time of the first station
BT × {(200 + R) × retry count setting value + 178.5}
• With a transient request
R: 13.2 + (NI × 4.8) + (NW × 9.6) + 180
• Without a transient request
R: 13.2 + (NI × 4.8) + (NW × 9.6)
:
Retry processing time of the second and subsequent stations
BT × {(200 + P) × retry count setting value + 178.5}
P: 10.8
F:
Return processing time (added only when there is a faulty station)
BT × {243.1 + 210.8 × (number of automatic return modules -1)} + ST
Number of Occupied Stations
Occupied Station 2
0
0
80 × number of stations
110 × number of
stations
160 × number of
stations
Occupied Station 3
Occupied Station 4
0
100 × number of
90 × number of stations
130 × number of
150 × number of
stations
210 × number of
260 × number of
stations
APPENDICES
A
0
stations
stations
stations
367