Problem
Check item
When multiple
remote stations
are
simultaneously
powered off at
Number of retries
G4-1
a speed of
setting
156kbps, the
"L RUN" LED
turns off
temporarily.
Description
Check the number of
Number of retries setting
retries.
CHAPTER 11 TROUBLESHOOTING
Check method
Corrective action
Increase the transmission
speed.
Reduce the number of
retries.