Wiring Procedure - Mitsubishi Electric MELSEC-Q Series User Manual

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

6.2.2

Wiring procedure

Connect a CC-Link dedicated cable to the terminal block of the master/local module.
(1) Wiring procedure
(a) Wiring diagram
DA
Terminating
resistor
DB
DG
SLD
FG
(b) Actual wiring diagram
● Connect the terminating resistors between the DA and DB terminals.
● Connect the shielded cables of a CC-Link dedicated cable to the SLD terminal through the FG terminal. Then ground the
cables at both ends with a ground resistance of 100 or less. The SLD and FG terminals are connected inside.
● No restrictions apply to the connection order of a master/local module. (The cables need not be connected in the order of
station number.)
● The star topology cannot be used. Note, however, that the T-branch connection can be used. (
6.2.3)
(Blue)
(Blue)
(White)
(White)
(Yellow)
(Yellow)
CC-Link dedicated cable
(Blue)
(White)
(Yellow)
CHAPTER 6 INSTALLATION AND WIRING
(Blue)
DA
(White)
DB
(Yellow)
DG
CC-Link dedicated cable
SLD
FG
Terminating
resistor
(Blue)
DA
Terminating
(White)
resistor
DB
(Yellow)
DG
SLD
FG
Page 79, Section
6
77