(3) Remote device station initial settings using a programming tool
(a) Reflection of the settings
The initial settings registered using a programming tool are reflected to a remote device station by writing the
settings to a CPU module and turning on Remote device station initialization procedure registration instruction
(SB000D).
(b) Signals that are required to be always on even after the initial process is completed
Turning off Remote device station initialization procedure registration instruction (SB000D) after the initial
process is completed turns off all the remote output (RY)s that turned on during the initial procedure
registration. For signals that are required to be always on (such as a conversion enable signal), turn them on
using a program.
(c) When a faulty station exists in the station to which the initial settings are to be
executed
Completion status of remote device station initialization procedure (SB005F) does not turn on unless the
execution is completed to all the stations that are registered in the remote device station initial setting of a
programming tool.
If a faulty station exists, create the program so that Remote device station initialization procedure registration
instruction (SB000D) is turned off depending on the completion status of other stations.
(4) A program when the module is connected to a Redundant CPU
For precautions for programming and a program example, refer to the manual for the Redundant CPU used.
QnPRHCPU User's Manual (Redundant System)