(Setting range)
If the interrupt condition is established upon the completion of a link scan, the interrupt is issued. If "Scan Completed"
is set to "Device Code", the interrupt is issued without condition upon the completion of a link scan.
Device
Device
Code
No.
0 to 1FFF
RX
H
0 to 01FF
SB
H
0 to 1FFF
RY
H
0 to 07FF
RWr
H
0 to 01FF
SW
H
Scan
Completed
3.
When completing the interrupt settings, open the "Intelligent Function Module Interrupt Pointer
Setting" window of the PLC parameter.
Relate "Interrupt (SI) No." of a master/local module set in the "Interrupt Settings" window to the interrupt
pointer of a CPU module.
Project window
4.
Input settings to the "Intelligent Function Module Interrupt Pointer Setting" window.
5.
Click the
Item
Interrupt Pointer
Start No.
PLC Side
Interrupt Pointer
Count
Start I/O No.
Intelligent
Module
Side
Start SI No.
112
Detection Method
Edge Detect + ON: Interrupt at rise
Edge Detect + OFF: Interrupt at fall
Level Detect + ON: Interrupt at ON
Level Detect + OFF: Interrupt at OFF
Edge Detect + Equal: Interrupt when the value is matched (first
time only)
Edge Detect + Unequal: Interrupt when the value is not matched
(first time only)
Level Detect + Equal: Interrupt when the value is matched
Level Detect + Unequal: Interrupt when the value is not matched
[Parameter]
button and close the setting window.
Set the start number (I) of the interrupt pointer.
Set the number of the interrupt conditions set in the "Interrupt
Settings" window of Network Parameter.
Set the start I/O number of the master/local module.
Set the start number of the SI No. set to "Interrupt (SI) No." in the
"Interrupt Settings" window of Network Parameter.
Interrupt Condition
–
[PLC Parameter]
"PLC System" tab
Description
Word
Channel
Device
No./
Setting
Connection
Value
No.
–
0 to 65535
–
(0
to
H
FFFF
)
H
Setting range
50 to 255 (Default: Blank)
1 to 16 (Default: Blank)
Within the range of I/O points of
the CPU module
(Default: Blank)
0 to 15 (Default: Blank)
Interrupt
(SI) No.
0 to 15
button