Mitsubishi Electric MELSEC-Q Series User Manual page 114

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

(Setting range)
If the interrupt condition is established upon the completion of a link scan, the interrupt is issued. If "Scan Completed"
is set to "Device Code", the interrupt is issued without condition upon the completion of a link scan.
Device
Device
Code
No.
0 to 1FFF
RX
H
0 to 01FF
SB
H
0 to 1FFF
RY
H
0 to 07FF
RWr
H
0 to 01FF
SW
H
Scan
Completed
3.
When completing the interrupt settings, open the "Intelligent Function Module Interrupt Pointer
Setting" window of the PLC parameter.
Relate "Interrupt (SI) No." of a master/local module set in the "Interrupt Settings" window to the interrupt
pointer of a CPU module.
Project window
4.
Input settings to the "Intelligent Function Module Interrupt Pointer Setting" window.
5.
Click the
Item
Interrupt Pointer
Start No.
PLC Side
Interrupt Pointer
Count
Start I/O No.
Intelligent
Module
Side
Start SI No.
112
Detection Method
Edge Detect + ON: Interrupt at rise
Edge Detect + OFF: Interrupt at fall
Level Detect + ON: Interrupt at ON
Level Detect + OFF: Interrupt at OFF
Edge Detect + Equal: Interrupt when the value is matched (first
time only)
Edge Detect + Unequal: Interrupt when the value is not matched
(first time only)
Level Detect + Equal: Interrupt when the value is matched
Level Detect + Unequal: Interrupt when the value is not matched
[Parameter]
button and close the setting window.
Set the start number (I) of the interrupt pointer.
Set the number of the interrupt conditions set in the "Interrupt
Settings" window of Network Parameter.
Set the start I/O number of the master/local module.
Set the start number of the SI No. set to "Interrupt (SI) No." in the
"Interrupt Settings" window of Network Parameter.
Interrupt Condition
[PLC Parameter]
"PLC System" tab
Description
Word
Channel
Device
No./
Setting
Connection
Value
No.
0 to 65535
(0
to
H
FFFF
)
H
Setting range
50 to 255 (Default: Blank)
1 to 16 (Default: Blank)
Within the range of I/O points of
the CPU module
(Default: Blank)
0 to 15 (Default: Blank)
Interrupt
(SI) No.
0 to 15
button