Appendix 5.2 Precautions When Replacing A Qj61Bt11 With A Qj61Bt11N - Mitsubishi Electric MELSEC-Q Series User Manual

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

(2) Dedicated instructions
(a) A(1S)J61BT11
The following dedicated instructions of an A(1S)J61BT11 cannot be used in a master/local module.
Instruction
RLPA
RRPA
(b) A(1S)J61QBT11
The following dedicated instructions of an A(1S)J61QBT11 cannot be used in a master/local module.
Instruction
CCL,CCLEND
SPCCLR
SPCBUSY
SEND
RECV
READ,SREAD
WRITE,SWRITE
REQ
(3) Condition setting switch
A master/local module does not have a condition setting switch. Configure settings that used to be set using a
condition setting switch in the network parameter of a programming tool.
Appendix 5.2
A QJ61BT11 can be replaced by a QJ61BT11N as is. For the mode names, refer to the following table.
396
Set the network parameter.
Set the auto refresh parameter.
Register a mail box for dedicated instructions for an intelligent device and remote device.
Issue an interrupt instruction to the dedicated instructions for an intelligent device.
Read the status of a remote station.
Send data (a message) to a specified station (QnACPU).
Read data (a message) sent using the SEND instruction.
Read word device data of a target station QnACPU into the host station.
Write data from the host station to word device data of a target station QnACPU.
Send a transient request (such as remote RUN/STOP) to other stations for execution.
Precautions when replacing a QJ61BT11 with a
QJ61BT11N
Mode of a QJ61BT11
Remote net mode
Remote I/O net mode
Description
Description
Mode of a QJ61BT11N
Remote net Ver.1 mode
Remote I/O net mode