Chapter 9 Dedicated Instructions; List Of Dedicated Instructions, Applicable Devices, And Precautions - Mitsubishi Electric MELSEC-Q Series User Manual

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

CHAPTER 9
Dedicated instructions facilitate programming for using intelligent function modules.
A master/local module can perform the following operations by using dedicated instructions.
• Transient transmission to a master station, local station, and intelligent device station
• Network parameter settings for a master station
• Message transmission to remote device stations
9.1
List of Dedicated Instructions, Applicable Devices, and
Precautions
(1) List of dedicated instructions
The dedicated instructions that can be used for a master/local module are listed below.
Target station
Master station,
local station
Intelligent device
station
Master station
Remote device
station
DEDICATED INSTRUCTIONS
Instruction
Reads data from the buffer memory areas of the target station or the
G(P).RIRD
device in the CPU module of the target station.
Writes data to the buffer memory areas of the target station or the
G(P).RIWT
device in the CPU module of the target station.
G(P).RIRD
Reads data from the buffer memory areas of the target station.
G(P).RIWT
Writes data to the buffer memory areas of the target station
Automatically performs handshaking with the target station and
reads data from the buffer memory areas of the target station.
G(P).RIRCV
The instruction is available for modules that have interlock signals
for the handshake (e.g. AJ65BT-R2(N)).
Automatically performs handshaking with the target station and
writes data to the buffer memory areas of the target station.
G(P).RISEND
The instruction is available for modules that have interlock signals
for the handshake (e.g. AJ65BT-R2(N)).
Reads data from the automatic update buffer of the target station.
G(P).RIFR
The instruction is available for modules that have the automatic
update buffer (e.g. AJ65BT-R2(N)).
Writes data to the automatic update buffer of the target station.
G(P).RITO
The instruction is available for modules that have the automatic
update buffer (e.g. AJ65BT-R2(N)).
Sets the network parameters to the master station and starts up the
G(P).RLPASET
data link.
Reads/writes parameters from the master station to the remote
device station and reads out the status.
G(P).RDMSG
The instrunctions can be used with the remote device station, for
example NZ2AW1C2AL, that supports the message transmission
function.

CHAPTER 9 DEDICATED INSTRUCTIONS

Description
9
Reference
Page 175,
Section 9.2
Page 181,
Section 9.3
Page 175,
Section 9.2
Page 181,
Section 9.3
Page 187,
Section 9.4
Page 192,
Section 9.5
Page 197,
Section 9.6
Page 201,
Section 9.7
Page 205,
Section 9.8
Page 221,
Section 9.9
173

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents