CHAPTER 3
This chapter describes the specifications, functions, I/O signals, buffer memory, remote I/O (RX and RY) and remote
register (RWr and RWw) of the master/local module.
3.1
General Specifications
For the general specifications of the master/local module, refer to the following.
User's manual for the CPU module used (hardware design, maintenance and inspection)
3.2
Performance Specifications
Item
Transmission speed
Maximum number of connected modules
(master station)
Number of occupied stations (local
station)
CC-Link Ver.1
Maximum number of
link points per system
CC-Link Ver.2
CC-Link Ver.1
Number of link points
per remote
station/local
station/intelligent
device station/standby
*1
master station
CC-Link Ver.2
24
SPECIFICATIONS
Selected from 156kbps, 625kbps, 2.5Mbps, 5Mbps, and 10Mbps.
64 (
Page 27, Section 3.2.1)
1 to 4 stations (The number of stations can be changed using a programming tool.)
• Remote I/O (RX, RY): 2048 points
• Remote register (RWw): 256 points (master station remote device station/local
station/intelligent device station/standby master station)
• Remote register (RWr): 256 points (remote device station/local station/intelligent device
station/standby master station master station)
• Remote I/O (RX, RY): 8192 points
• Remote register (RWw): 2048 points (master station remote device station/local
station/intelligent device station/standby master station)
• Remote register (RWr): 2048 points (remote device station/local station/intelligent device
station/standby master station master station)
• Remote I/O (RX, RY): 32 points (30 points for a local station)
• Remote register (RWw): 4 points (master station remote device station/local
station/intelligent device station/standby master station)
• Remote register (RWr): 4 points (remote device station/local station/intelligent device
station/standby master station master station)
Item
Single
32 points
Remote I/O
(30 points for a
(RX, RY)
local station)
Remote
register
4 points
(RWw)
Remote
4 points
register (RWr)
Specifications
Expanded Cyclic Setting
Double
Quadruple
32 points
64 points
(30 points for a
(62 points for a
local station)
local station)
8 points
16 points
8 points
16 points
Octuple
128 points
(126 points for a
local station)
32 points
32 points