Mitsubishi Electric MELSEC-Q Series User Manual page 358

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Number
Name
SW0078
(678
)
H
SW0079
(679
)
Error invalid
H
station specified
SW007A
status
(67A
)
H
SW007B
(67B
)
H
SW007C
(67C
)
H
SW007D
(67D
)
H
Temporary error
invalid status
SW007E
(67E
)
H
SW007F
(67F
)
H
SW0080
(680
)
H
SW0081
(681
)
H
Other station
data link status
SW0082
(682
)
H
SW0083
(683
)
H
356
Whether a station has been set as an error invalid station is stored.
0: A station other than an error invalid station
1: Error invalid station
b15
b14
b13
SW0078
16
15
14
SW0079
32
31
30
SW007A
48
47
46
SW007B
64
63
62
1 to 64 in the table indicate station numbers.
Only the bit corresponding to the start station number turns on.
Reserved stations, station with the last station number, and stations later
than that are excepted.
Whether a station is in the temporary error invalid status is stored.
0: Normal
1: Temporary error invalid status
b15
b14
b13
SW007C
16
15
14
SW007D
32
31
30
SW007E
48
47
46
SW007F
64
63
62
1 to 64 in the table indicate station numbers.
The bits turn on by the number of occupied stations.
Error invalid stations, reserved stations, station with the last station
number, and stations later than that are excepted.
Data link status of each station is stored.
0: Normal
1: Data link error
b15
b14
b13
SW0080
16
15
14
SW0081
32
31
30
SW0082
48
47
46
SW0083
64
63
62
1 to 64 in the table indicate station numbers.
• The bits turn on by the number of occupied stations.
• It takes maximum of six seconds for this register to turn on after a
slave station connected to the master station or local station becomes
faulty. The time until this register turns on differs depending on the
system configuration and error status.
• Temporary error invalid stations, error invalid stations, reserved
stations, station with the last station number, and stations later than
that are excepted.
Description
b12
to
b3
b2
b1
13
to
4
3
29
to
20
19
18
45
to
36
35
34
61
to
52
51
50
b12
to
b3
b2
b1
13
to
4
3
29
to
20
19
18
45
to
36
35
34
61
to
52
51
50
b12
to
b3
b2
b1
13
to
4
3
29
to
20
19
18
45
to
36
35
34
61
to
52
51
50
Availability
( : Yes, ×: No)
Online
Master
station
station
b0
2
1
17
33
49
b0
2
1
17
33
49
b0
2
1
17
33
49
Offline
Local
×
×
×

Hide quick links: