3.
Open the "Remote Device Station Initial Setting" window to configure the setting as follows.
Project window
button
Initial setting for the AJ65VBTCU-68ADVN
Initial setting for the AJ65VBTCU-68DAVN
4.
Click the
Registration" window.
5.
Select "HEX" in "Input Format" and enter information in other columns.
• Initial setting for an AJ65VBTCU-68ADVN (station number 1)
Configuring the initial setting executes the following processes from the first condition.
Condition
1st
2nd
3rd
4th
5th
6th
7th
8th
244
[Parameter]
button to open the "Remote Device Station Initial Setting Procedure
Select "HEX".
The channels 1 and 2 are set to the A/D conversion enable.
An input range is set.
• Channel 1: 0 to 5V
• Channel 2: User range setting 1 (-10 to 10V)
Whether a sampling process or averaging process is executed is set.
• Channel 1: Sampling process
• Channel 2: Averaging process (count average)
The average count of the channel 2 is set to 16.
Initial data processing completion flag is turned on.
Initial data setting request flag is turned on.
Initial data processing completion flag is turned off.
Initial data setting request flag is turned off.
[Network Parameter]
[CC-Link]
Description