Mitsubishi Electric MELSEC-Q Series User Manual page 187

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

(c) Check of the completion status
There are two types of interlock signals for the G(P).RIWT instruction: Completion device (D) and Status
display device at completion (D) + 1.
• Completion device
Turns on in the END process of the scan where the G(P).RIWT instruction is completed, and turns off in
the next END process.
• Status display device at completion
Turns on and off depending on the completion status of the G(P).RIWT instruction.
Normal completion: Remains off and does not change.
Abnormal end:
End process
Program
OFF
G(P).RIWT instruction
OFF
Completion device
OFF
Status display device
at completion
(d) Basic number of steps
The basic number of steps of the G(P).RIWT instruction is eight.
(e) Assignment of the send buffer
The assignment of the send buffer is performed in "Station Information Setting" of the network parameter of a
programming tool. (
(3) Operation error
For the following cases, an operation error occurs; Error flag (SM0) turns on and the error code is stored in SD0.
Error code
2112
4002
4003
4004
4100
4101
Turns on in the END process of the scan where the G(P).RIWT instruction is
completed, and turns off in the next END process.
End process
Execution completion of
ON
the G(P).RIWT instruction
Page 102, Section 7.3.2 (2))
Condition that an operation error occurs
When the module specified by Un is not an intelligent function module
When the module specified by Un is not a special function module
When attempting to execute an unsupported instruction
When the number of devices for the instruction is incorrect
When the device that cannot be used for the instruction is specified
When the data that cannot be used for the instruction is contained
When the number of data used for the instruction is set beyond the allowable range.
Or when the storage data or constants of the device specified with the instruction exceeds the
allowable range
CHAPTER 9 DEDICATED INSTRUCTIONS
End process
End process
ON
Abnormal end
Normal completion
1 scan
9
185