Mitsubishi Electric MELSEC-Q Series User Manual page 355

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Number
Name
The result of system configuration check when a station has been added
to a system and the system has started using the automatic CC-Link
Automatic CC-
SW0052
startup is stored.
Link startup
(652
)
H
0: Normal
execution result
Values other than 0: Error code (
Whether a master station duplication error canceling request has been
Master station
normally completed is stored.
SW0057
duplication error
0: Normal completion
(657
)
H
canceling result
Values other than 0: Error code (
The details of the LED display status are stored.
0: OFF
1: ON
b15b14b13b12b11
SW0058
Detailed LED
(658
)
display status
H
Transmission speed setting status is stored.
0: Cleared
1: Set
SW0059
Transmission
(659
)
speed setting
H
Whether the forced master switching instruction using SB000C has been
Forced master
normally completed is stored.
SW005D
switching
0: Normal completion
(65D
)
instruction
H
result
Values other than 0: Error code (
Remote device
station
Whether the initialization procedure registration instruction using
initialization
SB000D has been normally completed is stored.
SW005F
procedure
0: Normal completion
(65F
)
H
registration
Values other than 0: Error code (
instruction
result
Description
Page 293, Section 11.3.2)
Page 293, Section 11.3.2)
b10
b9
b8 b7 b6 b5 b4
b3
b2 b1 b0
0
0
0
0
0
0
LINE(ERROR)
: A cable is disconnected or the transmission
path has been affected by noise.
TIME(ERROR)
: Responses cannot be received from any station
due to the cable being disconnected or the
transmission path being affected by noise.
PRM(ERROR)
: Invalid parameter value
M/S(ERROR)
: Multiple master stations exist on the same line.
SW(ERROR)
: Error in switch settings
LOCAL
: The station is operating as a local station.
S MST
: The station is operating as a standby master
station.
MST
: The station is operating as a master station.
ERR.
: Error
RUN
: The module is operating normally.
b15
b8
b7 b6 b5 b4 b3
0
0
to
Page 293, Section 11.3.2)
Page 293, Section 11.3.2)
b2
b1 b0
0
0
0
10Mbps
5Mbps
2.5Mbps
625kbps
156kbps
APPENDICES
Availability
( : Yes, ×: No)
Online
Offline
Master
Local
station
station
×
×
×
×
(Standby
×
×
master
station
only)
×
×
353