G(P).Risend - Mitsubishi Electric MELSEC-Q Series User Manual

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

9.5

G(P).RISEND

The G(P).RISEND instruction automatically performs handshaking with the intelligent device station and writes data to
the buffer memory areas of the specified intelligent device station.
The instruction is available for modules that have a handshake signal (e.g. AJ65BT-R2(N)).
[Instruction
[Execution
symbol]
condition]
G.RISEND
GP.RISEND
Setting
Internal device
data
(System, user)
Bit
Word
(S1)
(S2)
(S3)
(D)
(1) Setting data
*1
Device
Start I/O number of the module (First two digits of I/O number written
Un
with three digits)
(S1)
Start number of the device in which control data is stored
(S2)
Start number of the device to which data to be written is stored
(S3)
Start number of the device in which an interlock signal is stored
Device that turns ON for one scan upon completion of writing.
(D)
(D) + 1 also turns ON at an abnormal end.
*1
The local device and the file register of each program cannot be used as a device for setting data.
192
Command
G.RISEND
Command
GP.RISEND
Applicable device
Link direct
device
File
J\
register
Bit
Word
Description
Un
(S1)
(S2)
(S1)
(S2)
Un
Intelligent
function module
Index
device
register Z
U\G
Setting range
0 to FE
Within the range of the
specified device
Within the range of the
specified device
Within the range of the
specified device
Within the range of the
specified device
(S3)
(D)
(S3)
(D)
Constant
Others
K, H
$
Data type
16-bit binary
H
Device name
Bit

Hide quick links: