Mitsubishi Electric MELSEC-Q Series User Manual page 65

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

4.
Connect a CC-Link dedicated cable to each module. Connect terminating resistors to the modules
at both ends. (
Page 76, Section 6.2)
Wiring diagram
Master station
Terminating
(White)
*1
resistor
(Yellow)
(110 , 1/2W)
Actual wiring
(Blue)
(White)
(Yellow)
*1
When a Ver.1.10-compatible CC-Link dedicated cable or CC-Link dedicated cable (Ver.1.00-compatible) is used,
connect 110 1/2W (Brown-Brown-Brown) terminating resistors.
When a CC-Link dedicated high-performance cable (Ver.1.00-compatible) is used, connect 130 1/2W (Brown-Orange-
Brown) terminating resistors.
After connecting the terminating resistors, check the following:
• If the modules are properly connected
• Voltage of the input power supply
• If the switch on the CPU module is set at STOP
• If the switch on the CPU module is not set at RESET
Use terminating resistors supplied with the modules.
AJ65BTB2-16T
(Blue)
CC-Link
dedicated cable
Terminating
*1
resistor
(110 , 1/2W)
CHAPTER 4 PROCEDURE BEFORE THE OPERATION
AJ65BTB1-16DT
(Blue)
(White)
(Yellow)
CC-Link
dedicated cable
Terminating resistor
(110 , 1/2W)
Terminating
*1
resistor
(110 , 1/2W)
*1
63
4