Converting From Fins To Host Link Fins - Omron SYSMAC CS1W-SCB41-V1 Operation Manual

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Protocol Conversion
6-5-6

Converting from FINS to Host Link FINS

System Configuration Patterns
Access from CX-Programmer (Sending Internal FINS Messages)
Serial-to-Serial
Serial Communications Unit/Board
CPU Unit
Peripheral or RS-232C port
Protocol
Host Link header
conversion
User-specified
Host Link header
FINS command
Used as Host Link Master
Note
(1) The FINS header contains the following information.
• Remote destination network address (DNA): Same as for CompoWay/F.
• Remote destination node address (DA1): Same as for CompoWay/F.
• Remote unit address (DA2): Same as for CompoWay/F.
(2) The contents of the Modbus-ASCII command enclosed in the FINS mes-
sage that is sent is as follows:
Slave address (ASCII) + FUNCTION code (ASCII) + Communications
data (ASCII)
The header ":" (3A hex) and LRC+CR/LF are not required when sending
FINS. They are added automatically for serial communications.
A PLC slave that is connected serially to the PLC master via Host Link can be
accessed from the PLC master or personal computer (see note) using FINS
messages. Accessing a device on another network via Host Link (serial com-
munications) is also possible by using FINS messages. By converting the
FINS to Host Link FINS, the PLC can function as a Host Link master.
Note Applications such as CX-Programmer or CX-Protocol that use CX-
Server as a communications driver.
• Sent FINS message: FINS header + User-specified FINS command (see
note 1)
• Message after conversion: FINS command enclosed in Host Link header
and terminator (see note 2)
FINS message
CX-Program-
User-specified
mer or other
FINS command
application
using CX-
(Via serial, network,
Server or
or CPU bus)
CPU Unit
(CMND(490))
The Board/Unit converts the FINS messages to Host Link FINS for sending in
this operation.
Access from Serially Connected CX-Programmer
CX-Programmer, etc.
User-specified
Terminator
FINS command
Terminator
RS-422A/485 (Host Link)
CS/CJ-series or CVM1/CV-series PLC (Host Link Slave)
Host Link FINS command
Serial Com-
User-specified FINS
Host Link header
command
munications
FINS command encapsulated using Host Link
Unit/Board
(RS-232C or RS-422A/485)
Details
Personal computers (e.g., CX-
Programmer) connected seri-
ally (via tool bus or Host Link)
to the PLC master can access
a PLC slave that is connected
serially to the PLC master via
Host Link.
Section 6-5
OMRON PLC (CS/CJ
Series, CVM1/CV
Terminator
Series)
(To other network)
FINS command
Routing tables to
treat serial
communications
path as network
Optional
221