Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 487

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Device Memory Fill as Word Data (All Device Types Except T/C)
(Sequence No. 812 (Hex 032C)) (Command Code: QW)
This sequence writes the word data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the
number of device points starting from the specified device address for the specified device type (except T, C) in
the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260)
458
Number of send data words
+0
First word of
send data
+1
Station No.
+2
(Undefined)
Device No.
+3
+4
+5
(Undefined)
+6
Number of send data bytes
+7
Write data
Offset
Contents (data format)
+0
Number of send data words
(4 digits hex)
+1
Station No.
(2 digits hex)
+2
(Undefined)
Device No. (6 digits hex)
+3
+4
(Undefined)
+5
+6
Number of send data bytes
(4 digits hex)
+7
Write data (4 digits hex)
Number of receive data words
+0
Receive data
storage words
Station No.
+1
+2
Error code
Offset
Contents (data format)
+0
Number of receive data words
+1
Station No.
(2 digits hex)
+2
Error code
(2 digits hex)
PLC No.
Device type
(Undefined)
Number of device
words/bits
0008 to 00FA hex (8 to 250 decimal)
PLC No.
Station No.: 00 to FF hex
(2 digits hex)
PLC No.: 00 to FF hex
Device type
Set the device type (1 character) in
(2 digits hex)
ASCII.
Set the first write address of the write
data.
(Undefined)
Device words/
Set the number of device words/bits to
bits
write.
(2 digits hex)
Specify the number of text data bytes
for the communications line (i.e., twice
the number of text bytes in S+6
onwards)
Set the write data.
PLC No.
(Undefined)
0002 hex or 0003 hex (2 or 3 decimal)
PLC No.
Station No.: 00 to FF hex
(2 digits hex)
PLC No.: 00 to FF hex
(Undefined)
Stores the error code converted to
hexadecimal. No error code is stored
for normal completion.
Appendix E
Data
Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents