Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 519

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5 @ K Digital Controller Write Protocol
Write MV at Stop Time and at PV Error (Sequence No. 060 (Hex
003C))
Writes the MV at stop time and the MV at PV error.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write MV Limits (Sequence No. 061 (Hex 003D))
Writes the MV upper limit, MV lower limit, and MV change rate limit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
490
+0
Number of send data words
+1
(Undefined)
Unit No.
+2
MV at stop time
+3
MV at PV error
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
MV at stop time (4 digits BCD)
+3
MV at PV error (4 digits BCD)
+0
Number of send data words
+1
(Undefined)
+2
MV upper limit
+3
MV lower limit
+4
MV change rate limit
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
MV upper limit (4 digits BCD)
+3
MV lower limit (4 digits BCD)
+4
MV change rate limit
(4 digits BCD)
0004 (fixed)
00 to 31
0000 to 1050
0000 to 1050
Unit No.
0005 (fixed)
00 to 31
MV lower limit + 1 to 1050
Heating/cooling control time: 0000 to 1050
0000 to MV upper limit – 1
0000 to 1000
Appendix G
Data
Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents