E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
Read Ramp Value (Sequence No. 115 (Hex 0073))
Reads the ramp values and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
516
+0
Number of receive data words
+1
Manual reset value
+2
Manual reset value
~
Manual reset value
+8
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Channel 0
Manual reset value
(4 digits BCD)
+2
Channel 1
Manual reset value
(4 digits BCD)
+8
Channel 7
Manual reset value
(4 digits BCD)
+0
Number of send data words
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+0
Receive data
storage words
(Undefined)
+1
+2
+3
(Undefined)
+4
~
+15
(Undefined)
+16
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Channel 0
Ramp value (3 digits BCD)
+2
Channel 0
Time unit (one ASCII character)
Channel 0
Channel 1
~
Channel 7
Unit No.
Number of receive data words
Ramp value
Time unit
(Undefined)
Ramp value
Time unit
(Undefined)
Ramp value
Time unit
(Undefined)
Appendix H
Data
0009
0000 to 1000
0000 to 1000
0000 to 1000
Data
0002 (fixed)
00 to 0F
Channel 0
Channel 1
~
Channel 7
Data
0011 (0017 decimal)
000 to 999
S: Seconds; M: Minutes; H: Hours

Hide quick links:

Advertisement

Table of Contents
loading