Status Area Error Indications - Omron SYSMAC CS1W-SCB41-V1 Operation Manual

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Status Area Error Indications

Indicators
RUN
ERC
ERH
RDY
Lit
Not lit Not lit Lit
Lit
Flash-
---
Flash-
ing
ing
Lit
Flash-
---
Lit
ing
Lit
Lit
---
Flash-
ing
11-2 Status Area Error Indications
Status Area Error
Information
Word
Boards
Units
(CS Series only)
(CS/CJ Series)
CIO 1901
n + 1
CIO
CIO
n + 6
1906
1916
CIO
CIO
n + 7
1907
1917
Possible cause
A Protocol Data File (BACKUP
read (restored) from the CPU Unit's Memory
Card to the Serial Communications Unit prop-
erly.
A protocol data write error has occurred or
protocol data has been destroyed.
There is no protocol data.
A protocol data syntax error has occurred.
• The flash memory for protocol data is
faulty.
• The Protocol Data File (BACKUP
restore operation failed when restoring pro-
tocol data from the CPU Unit's Memory
Card to the Serial Communications Unit.
This section describes status area error information.
When an error occurs, the corresponding flag is turned ON.
Bit
Flag name
01
Error Log data
error
00
Protocol data
error
n + 16
01
System Setup
error
n + 17
10
Remote node
receive busy
08
Local node
receive busy
@@
---
.PRM) was
If the indicator status remains the same
when the protocol data is retransmitted,
replace the Unit.
Transfer protocol data to the Unit.
Correct the protocol data and transfer it
to the Unit.
The ERC indicator can also be turned
OFF by executing a normal sequence for
the serial port for which the error is
occurring or by switching the CPU Unit to
PROGRAM mode temporarily.
• Transfer the protocol data to the Unit.
If the problem persists after correct
protocol data is transferred, replace
.PRM)
@@
the Unit.
• Write (backup) the protocol data from
the Unit to the Memory Card again
and then execute the restore opera-
tion again.
• If the restore operation fails two times
in succession, use CX-Protocol to
transfer the protocol data to the Serial
Communications Unit.
n = CIO 1500 + 25 × unit number
Possible cause
The error log
If the problem persists even if the
EEPROM is faulty.
power supply is cycled, replace
the Board/Unit.
A protocol data
If the error persists when protocol
checksum error has
data is retransmitted, replace the
occurred.
Board or Unit.
A System Setup
Correct the Setup Area settings,
error has occurred.
cycle the power supply, restart
the Unit/Board, or restart the
port, or execute the STUP(237)
instruction.
The remote node is
Cancel the communications with
in reception buffer
the remote node until this flag is
busy status when
turned OFF.
flow control is set for
the protocol.
The local node is in
Increase the transmission interval
reception buffer busy
to reduce transmission load to
status.
the remote node for which flow
control is set.
Section 11-2
Remedy
Remedy
311