Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 348

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Troubleshooting
Board/Unit
Serial commu-
status
nications mode
The Board/
The serial com-
Unit cannot
munications
convert the
mode is set to
received (via
Serial Gateway
CPU bus)
or protocol
FINS com-
macro mode.
mand into
either of the
protocols.
The serial com-
munications
mode is set to
Serial Gateway
or protocol
macro mode
Error conditions
Indicator
FINS end
display
code sent to
FINS trans-
mission
source
The SD@/
0205 hex
RD@ and
(response
COM@ indi-
timeout), etc.
cators do not
flash at all.
(Communica-
tions have
not been
electrically
established.)
The SD@ and
0202 hex (no
COM@ indi-
Unit)
cators do not
or
flash.
0401 hex
(undefined
command)
The SD@ and
2605 hex
COM@ indi-
(service exe-
cators do not
cuting)
flash at all.
Cause
Words allo-
cated in CIO
Area
---
A hardware
error has
occurred.
---
The FINS
destination
address is
not specified
correctly.
---
The serial
port received
a sixth FINS
command
when five
FINS com-
mands are
already wait-
ing.
Section 11-3
Remedy
Conduct a loopback test
in serial communications
mode to check the trans-
mission lines. If an error
occurs during the test,
replace the Board or
Unit.
Correct the FINS desti-
nation address specifica-
tion, and then resend the
FINS message. (Refer
particularly to 6-7 Condi-
tions Requiring Routing
Tables.)
Include retry processing
at the FINS command
transmission source for
when the FINS response
code 2605 hex is
received.
319

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents