Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 515

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5 @ K Digital Controller Write Protocol
NO:
Send word allocation:
Receive word allocation:
Connections
The connections are the same as that for the E5@K Digital Controller Read Protocol.
Write Set Point (Sequence No. 050 (Hex 0032))
Writes the set point.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive data
storage words
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Alarm Value (Sequence No. 051 (Hex 0033))
Writes alarm value 1 and alarm value 2.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
data
Receive Data Word Allocation (3rd Operand of PMCR(260))
None.
486
Set the constant 0000 for the 3rd operand (S).
Set the constant 0000 for the 4th operand (D).
Number of receive data words
+0
+1
Read data
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Set point (4 digits BCD)
+0
Number of send data words
+1
(Undefined)
+2
Alarm value 1
+3
Alarm value 2
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Alarm value 1 (4 digits BCD)
+3
Alarm value 2 (4 digits BCD)
0003 (fixed)
00 to 31
Set point lower limit to upper limit
Unit No.
0004 (fixed)
00 to 31
0000 to 999
0000 to 9999
Appendix G
Data
Data