Basic Operating Procedure
Board
(CS Series only)
1900
n
Board
(CS Series only)
Port 1
Port 2
1909
1919
Board
(CS Series only)
Port 1
Port 2
D32000
D32010
D32001
D32011
D32002
D32012
D32003
D32013
D32004
D32014
D32005
D32015
50
2. Set the allocated Software Switches.
Unit
(CS/CJ Series)
12
04
The enable/disable status for the Serial Gateway is automatically indicated
by the following flag.
Unit
(CS/CJ Series)
Port 1
Port 2
n+9
n+19
08
3. Set the local network table in the routing tables as required (using CX-Net).
No-protocol Mode
The following example is for the default (standard) communications condi-
tions, with the send delay set to 100 ms, start code included (e.g., @), end
code included (CR + LF), and number of receive bytes set to 100 bytes.
Unit
(CS/CJ Series)
Port 1
Port 2
m
m+10
15
11 to 08
m+1
m+11
03 to 00
m+2
m+12
15
11 to 00
m+3
m+13
15
m+4
m+14
15 to 08
m+5
m+15
12
09 to 08
07 to 00
Bit
Port 2
Serial Gateway Prohibit Switch (protocol mac-
ros)
0: Serial Gateway not prohibited
1: Serial Gateway prohibited
Port 1
Serial Gateway Prohibit Switch (protocol mac-
ros)
0: Serial Gateway not prohibited
1: Serial Gateway prohibited
Bit
Serial Gateway Prohibited Flag
1: Serial Gateway prohibited
1: Serial Gateway not prohibited
Bit
Setting
0
Start bits: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2 bits
Baud rate: 9,600 bps
3 hex
No-protocol
0 hex
The baud rate is 9,600 bps when the default
settings are used.
1
Send delay: User-specified
00 hex
Send delay setting range: 10 decimal (000A
hex), Unit: 10 ms
1
CTS control 1: Yes
40 hex
Start code: @ (40 hex)
1
Start code: Yes
10
End code: CR + LF
64 hex
Number of receive data bytes: 100 bytes
Section 1-9
n = 1500 + 25 × unit number
Function
Meaning
Meaning