I/O Memory Allocations
Software Switches
Status Area
80
Software Switches are used to output control signals from the CPU Unit to the
Serial Communications Board or Unit. The software switches are used for
loopback tests and to abort, release wait status, and control other functions
for protocol macros. For details on the software switch functions, refer to Sec-
tion 5 Using Protocol Macros and Section 10 Loopback Test.
Words
Board
Unit
(CS
(CS/
only)
CJ)
CIO
n
15
1900
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Note The One-shot Trace Switch and Continuous Trace Switch are used for the
Serial Communications Board/Unit only when executing traces from the CX-
Protocol in protocol macro mode. Do not manipulate these switches from a
ladder diagram.
The Status Area is used for status information input from Serial Communica-
tions Board or Unit to the CPU Unit. The Status Area is where the Serial Com-
munications Board or Unit sets communications status, the transmission
control signal status, the transmission error status, and the protocol status.
Bit
Port 2
Reserved
Loopback Test Switch (loopback tests)
1: Start, 0: Stop
Reserved
Serial Gateway Prohibited Switch (protocol mac-
ros)
1: Prohibited, 0: Not prohibited
Abort Switch (protocol macros)
1: Abort, 0: Aborted
One-shot Trace Switch (protocol macros, see
note)
1: Start, 0: Stop
Continuous Trace Switch
(protocol macros, see note)
1: Start, 0: Stop
Wait Release Switch (protocol macros)
1: Release wait, 0: Wait released
Port 1
Reserved
Loopback Test Switch (loopback tests)
1: Start, 0: Stop
Reserved
Serial Gateway Prohibited Switch (protocol mac-
ros)
1: Prohibited, 0: Not prohibited
Abort Switch (protocol macros)
1: Abort, 0: Aborted
One-shot Trace Switch (protocol macros, see
note)
1: Start, 0: Stop
Continuous Trace Switch
(protocol macros, see note)
1: Start, 0: Stop
Wait Release Switch (protocol macros)
1: Release wait, 0: Wait released
Section 2-3
n = CIO 1500 + 25 × unit number
Function