Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 56

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Specifications
Protocol Macro Function Specifications
Item
Number of protocols
Number of sequences
Per protocol
Sequence execution condition
Communications mode
Synchronous mode
Baud rate (see note 1)
Communications distance (see note 1)
Connection configuration
Number of connected Units
Maximum number of
data exchange words
between PLC and
protocol macro
function
20 max.
Can be created and registered with the Protocol Support Tool
(CX-Protocol).
1,000 max.
Number of
60 max.
sequences
Number of mes-
300 max.
sages
Number of recep-
100 max.
tion matrixes
Using the CPU Unit's PMCR(260) instruction (specifying the sequence
number)
Half-duplex or full-duplex
Start-stop synchronization (asynchronous mode)
RS-232C port and RS-422A/485 ports:
1,200/2,400/4,800/9,600/19,200/38,400 bps
Default setting: 9,600 bps
Note A baud rate of 57,600 bps can be selected when using Unit Ver.
RS-232C port: 15 m max.
RS-442A/485 port: 500 m max. (The total combined cable length is
500 m max. T-branch lines must be a maximum of 10 m long.)
RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using a Convert-
ing Link Adapter.)
RS-422A/485 port: 1:N (N = 32 Units max.)
32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connec-
tion)
Operand setting
250 words
Link word setting
500 words
Direct setting
500 words
Description
1.2 or later (115,200 bps is not possible).
Including the word that specifies the number of
words (1 word)
O1, O2, I1, and I2: 500 words total
Maximum number of words per data attribute
Section 1-6
27