Host Link FINS Command Master
FINS COMMAND SEND/RECEIVE
(Sequence No. 750 (Hex 02EE)
This sequence sends user-specified FINS commands to the specified Host Link Unit and stores the response
starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Number of send data words
First word of
+0
send data
Host Link unit number
+1
Remote destination node
+2
address (DA1)
+3
MRC
+4
Number of FINS text bytes
+5
Offset
Contents (data format)
+0
Number of send data words
(4 digits hex)
+1
Host Link unit
No.
(2 digits BCD)
+2
Remote destina-
tion node
address (DA1)
(2 digits hex)
+3
MRC
(2 digits hex)
+4
Number of FINS text bytes
(4 digits hex)
+5
FINS text
Number of receive data words
+0
Receive data
storage words
+1
End code
+2
FINS receive text
Offset
Contents (data format)
+0
Number of receive data words
(4 digits hex)
+1
End code (4 digits hex)
+2
FINS receive text
Remote destination
network address (DNA)
Remote destination unit
address (DA2)
SRC
FINS text
0005 to 00FA hex (5 to 250 decimal)
Remote destina-
Host Link unit number: 00 to 31
tion network
Remote destination network address
address (DNA)
(DNA): 00 to 7F hex
(2 digits hex)
Remote destina-
Remote destination node address
tion unit address
(DA1): 00 to FE hex
(DA2)
Remote destination unit address (DA2):
(2 digits hex)
00 to FE hex
SRC
User-specified FINS command
(2 digits hex)
0000 to 03D4 hex
Specify the number of FINS command
text bytes for the communications line
(i.e., twice the number of bytes of FINS
text in S+5 onwards)
The text for the user-specified FINS
command to send.
0002 to 00FA hex (2 to 250 decimal)
The end code is stored in hexadecimal.
The received text is stored.
Appendix D